- Air Duct Velocity
- 100 to 4000
- Alarm Current
- 65 mA at 24 VDC, 135 mA RMS at 24 VAC 60 Hz, 35 mA RMS at 120 VAC 60 Hz
- Capacitance
- 270
- Contact Rating
- 2 A at 30 V DC Resistive (SPST), 10 A at 30 V DC Resistive, 10 A at 250 V AC Resistive, 1/2 hp at 240 V AC, 1/4 hp at 120 V AC (DPDT)
- Depth
- 2-1/2
- Height
- 2.5
- Humidity Rating
- 0-95% RH
- Length
- 14.38
- Maximum Standby Current
- 21 mA at 24 VDC, 65 mA RMS at 24 VAC 60 Hz, 20 mA RMS at 120 VAC 60 Hz
- Power Source
- 20 to 29 VDC, 120/24 VAC
- Product Type
- Smoke Detector
- Reset Time
- 0.6 s Maximum
- Reset Voltage
- 3 VDC Minimum at 20 to 29 VDC, 2 VAC Minimum at 24 VAC, 10 VAC Minimum at 120 VAC
- Response Time
- 15
- Sensing
- Photoelectric
- Temperature Rating
- -4 to 158 deg F Operating, -22 to 158 deg F Storage
- Type
- Duct smoke detector
- Width
- 5
- Wiring
- 4-wire conventional
- ERP item ID